MEAN WELL BIC-5K is a 5KW bidirectional power supply with energy recycle, featuring AC-DC/DC-AC conversion with an ultra-fast 1ms switching time and up to 93.5% efficiency. Supporting parallel scalability up to 30KW (5+1 units) and CANBus/MODBus-RTU protocols, it is optimized for battery cell formation, V2G, kinetic energy recovery, and energy storage systems. Certified with UL62368-1, IEC62477-1, and IEC50549-1 with OVC III protection, BIC-5K provides an efficient green energy solution with a 5-year warranty.
Features
- Comnining AC → DC and DC → AC bidirection power, 5KW full-power operation in both directions
- Ultra-Fast Bidirectional Time of 1ms (AC/DC ↔DC/AC)
- Glibal Certificates in Multi-Fields (ITE 62368-1, Enery Converter 62477-1, AC Grid System 50549-1)
- 180~305Vac (277Vac Available)
- High Efficiency up to 93.5%
- THD <3% in both Conversion Mode
- Parallel Operation up to 30KW (5+1 unit)
- Support CANBus or MODBus-RTU(RS-485) Protocol Communication
- Force charging and recycle mode with CAN Bus command (Optional)
- Complete protections: Anti-islanding protection, AC fail protection, DC OVP, OLP, OCP, OTP
- Over Voltage Category III (OVC III)
- -30 °C ~ 70 °C Wide Operating Temperature
- FAN Noise < 43~54dB
- Support 3Ø with Multiple Units Configuration
- Conformal Coating
- 5-year warranty
Specification
| SPECIFICATION | BIC-5K-24□ | BIC-5K-48□ | BIC-5K-96□ | BIC-5K-380□ | |||
|---|---|---|---|---|---|---|---|
| □ = Blank, MOD (standard model in stock) | |||||||
| AC to DC Direction | OUTPUT | ||||||
| DC VOLTAGE | 24V | 48V | 96V | 380V | |||
| RATED CURRENT | 208A | 104A | 52A | 13.22A | |||
| RATED POWER | 4992W | 4992W | 4992W | 5025W | |||
| FULL POWER VOLTAGE RANGE | 24 ~ 33V | 48 ~ 66V | 96 ~ 112V | 335 ~ 430V | |||
| RIPPLE & NOISE (max.) Note.2 | 350mVp-p | 600mVp-p | 900mVp-p | 2.8Vp-p | |||
| VOLTAGE RANGE | 19 ~ 33V | 38 ~ 66V | 76 ~ 112V | 280 ~ 430V | |||
| CURRENT RANGE | 0 ~ 208A | 0 ~ 104A | 0 ~ 52A | 0 ~ 15A | |||
| VOLTAGE TOLERANCE Note.3 | ±2.0% | ||||||
| LINE REGULATION | ±1.0% | ||||||
| LOAD REGULATION | ±1.0% | ||||||
| SETUP, RISE TIME | 8000ms, 150ms/230Vac at full load | ||||||
| INPUT | |||||||
| AC VOLTAGE RANGE | 180 ~ 305Vac | ||||||
| FREQUENCY RANGE | 47 ~ 63Hz | ||||||
| POWER FACTOR (Typ.) | ≧0.99/230Vac at full load | ||||||
| EFFICIENCY (Typ.) Note.4 | 91% | 92.5% | 93% | 93% | |||
| AC CURRENT (Typ.) | 27A/230Vac | ||||||
| INRUSH CURRENT (Typ.) | 120A/230Vac | ||||||
| LEAKAGE CURRENT (Peak) | 7.07mA/305Vac | ||||||
| TOTAL HARMONIC DISTORTION | <3%(@load=100%/230Vac) | ||||||
| DC to AC Direction | INPUT | ||||||
| INPUT POWER (Max.) | 5665W | 5550W | 5550W | 5500W | |||
| FULL POWER VOLTAGE RANGE | 24 ~ 33V | 48 ~ 66V | 96 ~ 112V | 335 ~ 430V | |||
| DC VOLTAGE RANGE | 19 ~ 33V | 38 ~ 66V | 76 ~ 112V | 280 ~ 430V | |||
| MAX. INPUT CURRENT | 232A | 114A | 57A | 16A | |||
| OUTPUT | |||||||
| RATED OUTPUT POWER (Typ.) | 5000W | ||||||
| VOLTAGE RANGE | 180 ~ 305Vac determined by AC main (277Vac available) | ||||||
| FREQUENCY RANGE | 47 ~ 63Hz determined by AC main | ||||||
| AC CURRENT (Typ.) | 22.5A/230Vac | ||||||
| POWER FACTOR (Typ.) | 0.99/230Vac at full load | ||||||
| EFFICIENCY (Typ.) Note.4 | 91% | 93% | 93% | 93.5% | |||
| TOTAL HARMONIC DISTORTION | <3%(@load=100%/230Vac) | ||||||
| PROTECTION | |||||||
| OVER LOAD | 105 ~ 115% rated output power | ||||||
| AC to DC | Constant current limiting, shut down DC O/P voltage 5 sec. after DC O/P voltage is down low, re-power on to recover | ||||||
| DC to AC | Not accurable with constant power design | ||||||
| SHORT CIRCUIT | Shut down O/P current, re-power on to recover | ||||||
| OVER VOLTAGE | 34 ~ 35V | 68 ~ 70V | 115 ~ 121V | 435 ~ 450V | |||
| Protection type : Shut down O/P voltage, re-power on to recover | |||||||
| OVER TEMPERATURE | Shut down O/P voltage, recovers automatically after temperature goes down | ||||||
| ISLANDING PROTECTION | Shut down AC O/P voltage, re-power on to recover | ||||||
| FUNCTION | |||||||
| BIDIRECTION SWITCH TIME (Typ.) | 1ms | 1ms | 3ms | 1ms | |||
| PARALLEL | Up to 30KW(5+1) units, Please refer to the Function Manual | ||||||
| CANBUS or MODBUS | Communication provides function such as control, setting and monitoring | ||||||
| REMOTE ON-OFF CONTROL | By electrical signal or dry contact Short: Power ON Open: Power OFF Please refer to the Function Manual infollowing | ||||||
| FAN NOISE (Typ.) | Note.6 | Built-in intelligent fan speed control detect by PSU’s internal temperature | |||||
| 10% load with Ta=25℃ | 54dB | 43dB | 43dB | 43dB | |||
| 70% load with Ta=25℃ | 54dB | 44dB | 44dB | 44dB | |||
| ENVIRONMENT | |||
|---|---|---|---|
| WORKING TEMP. | -30 ~ +70℃ (Refer to "Derating Curve") | ||
| WORKING HUMIDITY | 20 ~ 90% RH non-condensing | ||
| STORAGE TEMP., HUMIDITY | -40 ~ +85℃, 10 ~ 95% RH non-condensing | ||
| TEMP. COEFFICIENT | ±0.03%/℃ (0 ~ 40℃) | ||
| VIBRATION | 10 ~ 500Hz, 3G 10min./1cycle, 60min. each along X, Y, Z axes | ||
| SAFETY & EMC | |||
| SAFETY STANDARDS | CB IEC62368-1/IEC62477-1 UL UL62368-1, CAN/CSA C22.2 No.62368-1 TUV BS EN/EN62368-1, BS EN/EN62477-1, BS EN/EN50549-1 EAC TP TC 004 approved | ||
| OVER VOLTAGE CATEGORY | IEC/EN/UL 62368-1 (OVC III, altitude up to 2000m) IEC/EN 62477-1 (OVC III, altitude up to 2000m) | ||
| WITHSTAND VOLTAGE Note.7 | I/P-O/P:6KVdc I/P-FG:4KVdc O/P-FG:4KVdc | ||
| ISOLATION RESISTANCE Note.7 | I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500Vdc / 25℃ / 70% RH | ||
| EMC EMISSION | BS EN/EN55032, BS EN/EN61000-6-4 | ||
| Parameter | Standard | Test Level / Note | |
| Conducted | BS EN/EN55032 (CISPR32) | Class A | |
| Radiated | BS EN/EN55032 (CISPR32) | Class A | |
| Harmonic Current | BS EN/EN61000-3-12 | Class A | |
| Voltage Flicker | BS EN/EN61000-3-11 | ----- | |
| EMC IMMUNITY | BS EN/EN55035, BS EN/EN61000-6-2 | ||
| Parameter | Standard | Test Level / Note | |
| ESD | BS EN/EN61000-4-2 | Level 3, 8KV air ; Level 2, 4KV contact | |
| Radiated | BS EN/EN61000-4-3 | Level 3 | |
| EFT / Burst | BS EN/EN61000-4-4 | Level 3 | |
| Surge | BS EN/EN61000-4-5 | 2KV/Line-Line 4KV/Line-Earth | |
| Conducted | BS EN/EN61000-4-6 | Level 3 | |
| Magnetic Field | BS EN/EN61000-4-8 | Level 4 | |
| Voltage Dips and Interruptions | BS EN/EN61000-4-34 | >95% dip 0.5 periods, 30% dip 25 periods, >95% interruptions 250 periods | |
| OTHERS | |||
| MTBF | 209.4K hrs min. Telcordia SR-332 (Bellcore) ; 17.8K hrs min. MIL-HDBK-217F (25℃) | ||
| DIMENSION | 460*211*83.5mm (L*W*H) | ||
| PACKING | 12Kg; 1pcs/ 12Kg/ 1.25CUFT | ||
Model
| Model No. | I/P Vol. | O/P Vol. | O/P Current | O/P Watts (max.) |
|---|---|---|---|---|
| BIC-5K-24x | 180 ~ 305VAC | 24VDC | 0 ~ 208A | 4992W |
| BIC-5K-48x | 180 ~ 305VAC | 48VDC | 0 ~ 104A | 4992W |
| BIC-5K-96x | 180 ~ 305VAC | 96VDC | 0 ~ 52A | 4992W |
| BIC-5K-380x | 180 ~ 305VAC | 380VDC | 0 ~ 13.22A | 5025W |
Notices:
- All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
- Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
- Tolerance : includes set up tolerance, line regulation and load regulation.
- Efficiency is tested 75% load, linear load at 230Vac input voltage and 24V/48V/96V/380Vdc output voltage
- The power supply is considered as an independent unit, but the final equipment still need to re-confirm that the whole system complies with the EMC directives.
- FAN noise test set up according to ISO-7779.
- During withstand voltage and isolation resistance testing, the screw “A” shall be temporarily removed, and shall be installed back after the testing.
- The Regulatory Compliance Mark (RCM) is applied on a voluntary basis. The equipment meets the relevant IEC or AS/NZS standards, or AS/NZS 3820 where applicable. The use of the RCM mark complies with AS/NZS 4417.1.
※ Product Liability Disclaimer: For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
Communication Protocol Options:
- x = Blank ; CANBus
- x = MOD ; MODBus